Product Design Drawings
Product Technical Parameters
IEC designation | U70B/146 | U70B/127 | |
Diameter D | mm | 255 | 255 |
Height H | mm | 146 | 127 |
Creepage distance L | mm | 320 | 320 |
Socket coupling | mm | 16 | 16 |
Mechanical failing load | kn | 70 | 70 |
Mechanical routine test | kn | 35 | 35 |
Wet power frequency withstand voltage | kv | 40 | 40 |
Dry lightning impulse withstand voltage | kv | 100 | 100 |
Impulse puncture voltage | P.U | 2.8 | 2.8 |
Power frequency puncture voltage | kv | 130 | 130 |
Radio influence voltage | μv | 50 | 50 |
Corona visual test | kv | 18/22 | 18/22 |
Power frequency electric arc voltage | ka | 0.12s/20kA | 0.12s/20kA |
Net weight per unit | kg | 3.6 | 3.5 |
Installation and maintenance
3 Installation
3.1 Appearance Check
The insulators shall be inspected one by one according to chapter 28 of GB/ T1001.1-2003 and this standard before installation, and the use of insulators that do not meet the above requirements shall be prohibited.
3.2 Insulator resistance measurement
Insulation resistance of porcelain insulators shall be measured one by one before installation. Insulators that do not meet the requirements of DLT626 shall not be used.
3.3 Precautions
During installation, insulators should be handled with care, not thrown, and avoid collision and friction with sharp objects.
4 Operation and Maintenance
4.1 document
The operating unit shall establish insulator files in accordance with DL/T 626.
4.2 maintenance
During inspection and inspection of insulators, if it is found that the lock pin is missing or the insulator has zero value, live operation or power failure repair shall be adopted, and the insulators shall be inspected in time according to the following provisions.
If one of the following conditions occurs, the insulator can be determined to be invalid. A) Cracks and yellow rust spots appear on the iron cap (acid reflux); B) Bending and cracking of steel feet; C) Severe arc burning of iron cap and steel foot;
D) iron cap, insulation and steel foot are not on the same axis: e) porcelain cracks occur;
F) Insulation parts are seriously burned by partial discharge and partial shedding occurs; G) Cracks or skew appear in the cement at the steel foot;
H) Corrosion of steel feet occurs as described in DLT626-2005.
Pictures from the Internet
Packaging
Product detail pictures:
Related Product Guide:
"Quality very first, Honesty as base, Sincere assistance and mutual profit" is our idea, in an effort to create consistently and pursue the excellence for Online Exporter Low Tension Toughened Glass Insulator - High Voltage 70kn Disc Suspension Toughened Glass Insulator U70BL – Johnson, The product will supply to all over the world, such as: Sacramento, Japan, Swaziland, It is our customers' satisfaction over our products and services that always inspires us to do better in this business. We build mutually beneficial relationship with our clients by giving them large selection of premium car parts at marked down prices. We offer wholesale prices on all our quality parts so you are guaranteed greater savings.
By Matthew Tobias from Pretoria - 2018.11.06 10:04
We have been cooperated with this company for many years, the company always ensure timely delivery ,good quality and correct number, we are good partners.
By Aaron from San Francisco - 2017.05.02 11:33