Manufactur standard U120b Glass Insulator - High Voltage 70kn Disc Suspension Toughened Glass Insulator U70BL – Johnson
Manufactur standard U120b Glass Insulator - High Voltage 70kn Disc Suspension Toughened Glass Insulator U70BL – Johnson Detail:
Product Design Drawings

Product Technical Parameters
| IEC designation | U70B/146 | U70B/127 | |
| Diameter D | mm | 255 | 255 |
| Height H | mm | 146 | 127 |
| Creepage distance L | mm | 320 | 320 |
| Socket coupling | mm | 16 | 16 |
| Mechanical failing load | kn | 70 | 70 |
| Mechanical routine test | kn | 35 | 35 |
| Wet power frequency withstand voltage | kv | 40 | 40 |
| Dry lightning impulse withstand voltage | kv | 100 | 100 |
| Impulse puncture voltage | P.U | 2.8 | 2.8 |
| Power frequency puncture voltage | kv | 130 | 130 |
| Radio influence voltage | μv | 50 | 50 |
| Corona visual test | kv | 18/22 | 18/22 |
| Power frequency electric arc voltage | ka | 0.12s/20kA | 0.12s/20kA |
| Net weight per unit | kg | 3.6 | 3.5 |
Installation and maintenance

3 Installation
3.1 Appearance Check
The insulators shall be inspected one by one according to chapter 28 of GB/ T1001.1-2003 and this standard before installation, and the use of insulators that do not meet the above requirements shall be prohibited.
3.2 Insulator resistance measurement
Insulation resistance of porcelain insulators shall be measured one by one before installation. Insulators that do not meet the requirements of DLT626 shall not be used.
3.3 Precautions
During installation, insulators should be handled with care, not thrown, and avoid collision and friction with sharp objects.

4 Operation and Maintenance
4.1 document
The operating unit shall establish insulator files in accordance with DL/T 626.
4.2 maintenance
During inspection and inspection of insulators, if it is found that the lock pin is missing or the insulator has zero value, live operation or power failure repair shall be adopted, and the insulators shall be inspected in time according to the following provisions.
If one of the following conditions occurs, the insulator can be determined to be invalid. A) Cracks and yellow rust spots appear on the iron cap (acid reflux); B) Bending and cracking of steel feet; C) Severe arc burning of iron cap and steel foot;
D) iron cap, insulation and steel foot are not on the same axis: e) porcelain cracks occur;
F) Insulation parts are seriously burned by partial discharge and partial shedding occurs; G) Cracks or skew appear in the cement at the steel foot;
H) Corrosion of steel feet occurs as described in DLT626-2005.

Pictures from the Internet
Packaging

Product detail pictures:








Related Product Guide:
With reliable quality process, good reputation and perfect customer service, the series of products produced by our company are exported to many countries and regions for Manufactur standard U120b Glass Insulator - High Voltage 70kn Disc Suspension Toughened Glass Insulator U70BL – Johnson, The product will supply to all over the world, such as: Montpellier, Morocco, Germany, Taking the core concept of "to be the Responsible". We will redound up on society for high quality products and good service. We will initiative to participate in international competition to be a first- class manufacturer of this product in the world.
By Grace from Czech republic - 2017.11.11 11:41
The company comply with the contract strict, a very reputable manufacturers, worthy a long-term cooperation.
By Dominic from Macedonia - 2017.08.15 12:36