High Voltage 120kn Disc Suspension Toughened Glass Insulator U120B

Short Description:

Our glass insulators have good insulation performance. Under dry and rainy conditions, it can withstand the voltage specified in the green standard, has sufficient mechanical strength, can withstand large temperature changes without cracking, slow aging speed and long service life. It has sufficient anti pollution and anti chemical gas erosion ability


Product Detail

Product Tags

Product Design Drawings

High Voltage 120kn Disc Suspension Toughened Glass Insulator U120B (1)

Product technical parameters

IEC designation U120B/127 U120B/146
Diameter D mm 255 255
Height H mm 127 146
Creepage distance L mm 320 320
Socket coupling mm 16 16
Mechanical failing load kn 120 120
Mechanical routine test kn 60 60
Wet power frequency withstand voltage kv 40 40
Dry lightning impulse withstand voltage kv 100 100
Impulse puncture voltage P.U 2.8 2.8
Power frequency puncture voltage kv 130 130
Radio influence voltage μv 50 50
Corona visual test kv 18/22 18/22
Power frequency electric arc voltage ka 0.12s/20Ka 0.12s/20Ka
Net weight per unit kg 4 4

Product Application

玻璃

Product advantages and disadvantages

1. Glass insulator

Advantages: the mechanical strength of the surface layer of glass insulator is high, the surface is not easy to crack, and the aging speed is slow; It can cancel the live periodic preventive test of insulators during operation, and there is no need to carry out "zero value" detection during operation, so the operation and maintenance cost is low.

Disadvantages: due to the transparency of glass, it is easy to find small cracks and various internal defects and damages during appearance inspection.

2. Ceramic insulator

Advantages: good chemical stability and thermal stability, strong anti-aging ability, good electrical and mechanical properties, and flexible assembly.

Disadvantages: defects are not easy to be found, and they begin to be found only after several years of operation; The zero value detection of ceramic insulators must be carried out one by one on the tower, which requires a lot of manpower and material resources; The probability of accidents caused by lightning stroke and pollution flashover is high.

3. Composite insulator

Advantages: small size, easy maintenance; Light weight and easy installation; High mechanical strength, not easy to break; Excellent seismic performance and good pollution resistance; Fast production cycle and high quality stability.

Disadvantages: anti aging capability is not as good as ceramic and glass insulators, and the production cost is higher than that of ceramic and glass insulators.

img1.qjy168