Main Speccifications of 12-72.5kV Solid-Core Post Insulators |
FTY No. |
Type No. |
Fig. No. |
Rated Volt. |
Mechanical Failing Load |
Creepage Distance |
Main Dimensions ( mm ) |
Weight |
Cantilever |
Torsion |
H |
D |
Top Fitting |
Bottom Fitting |
(kV) |
(kN) |
(kN/m) |
(mm) |
a1 |
d1 |
hole |
a2 |
d2 |
hole |
kg |
2701 |
ZSW-12/5L |
3 |
10 |
5 |
|
230 |
22 |
140 |
36 |
M8 |
2 |
55 |
M10 |
4 |
6 |
2702 |
ZSW-17.5/4 |
1 |
15 |
4 |
|
300 |
240 |
145 |
70 |
M10 |
2 |
125 |
12 |
4 |
8 |
2703 |
ZSW-24/4 |
1 |
20 |
4 |
3 |
400 |
290 |
145 |
70 |
M10 |
2 |
125 |
12 |
4 |
9 |
2704 |
ZSW-24/8 |
1 |
20 |
8 |
6 |
400 |
350 |
140 |
76 |
M12 |
2 |
180 |
14 |
4 |
12 |
2705 |
ZSW-24/16 |
1 |
20 |
16 |
12 |
480 |
350 |
230 |
140 |
M12 |
4 |
210 |
18 |
4 |
25 |
2706 |
ZSW-24/30 |
1 |
20 |
30 |
20 |
500 |
400 |
230 |
140 |
M12 |
4 |
225 |
18 |
4 |
28 |
2710 |
ZSW-40.5/4-2 |
1 |
35 |
4 |
3 |
875 |
440 |
260 |
140 |
M12 |
4 |
210 |
18 |
4 |
35 |
2711 |
ZSW-40.5/6L-4 |
1 |
35 |
6 |
4.5 |
1256 |
560 |
260 |
140 |
M12 |
4 |
225 |
18 |
4 |
43 |
2712 |
ZSW-40.5/8-2 |
1 |
35 |
8 |
6 |
875 |
420 |
260 |
140 |
M12 |
4 |
180 |
14 |
4 |
33 |
2713 |
ZSW-40.5/12-4 |
1 |
35 |
12 |
9 |
1256 |
560 |
270 |
140 |
M12 |
4 |
225 |
18 |
4 |
43 |
2720 |
ZSW-72.5/8-3 |
1 |
66 |
8 |
6 |
1815 |
740 |
260 |
140 |
M12 |
4 |
180 |
14 |
4 |
50 |
2721 |
ZSW-72.5/8L-3 |
3 |
66 |
8 |
6 |
1815 |
760 |
260 |
140 |
M12 |
4 |
140 |
M12 |
4 |
51 |
2722 |
ZSW-72.5/8.5-4 |
3 |
66 |
8 |
6.5 |
2248 |
770 |
260 |
140 |
M12 |
4 |
140 |
M12 |
4 |
52 |